- Manufacturer
- GIGABYTE
- Model
- DCA3-ST0
- Product type
- Rack infrastructure
- Dimensions (WxHxD, mm)
- 800 x 2286 x 1200
- Open Rack Version
- ORV3
- Heat Dissipation Capacity
- 130 kW at approach temperature 5°C
200 kW at approach temperature 8°C
- CDU Power Consumption
- Full load: 1300 W
- Water Flow Rate
- Primary: 200 LPM
Secondary: 130 LPM
- Operating Properties
- Operating ambient temperature: 0°C to 50°C
Operating liquid temperature: 20°C to 50°C
[Note] The Facility Water System (FWS) loop must meet the water quality values specified in ASHRAE Liquid Cooling Guidelines for Datacom Equipment Centers, 2nd ed., Ch. 5, as reproduced in the ASHRAE TC 9.9 white paper Water-Cooled Servers: Common Designs, Components, and Processes (2019), Table 1.
- No. of Bus Bars
- 1 x 48 V bus bar
- Power Shelf
- Optional power shelf:
21" 33 kW power shelf with 3 x C13 AC power connections: Delta AC-205A
19" 33 kW power shelf without C13 AC power connections: Delta ECD68000075
- Available Node Space
- 18OU + 21OU
[Note] 23rd OU occupied by reinforced bar.
Configuration options and limits depend on the exact product and revision. Confirm the proposed combination and the supplied parts before ordering; optional features are not necessarily included.